The EX series card-type I/O consists of an adapter module, I/O modules, a power supply module, and a terminal module. The adapter supports various communication buses, such as PROFINET, EtherNet/IP, EtherCAT, DeviceNet, Modbus RTU, PROFIBUS-DP, etc. The adapter module converts standard communication buses to the communication bus of the product module, enabling the expansion of different types and numbers of I/O modules.
Today, Xiaode's Classroom will explain in detail some common problems encountered when using the EX series modules.
Decker Automation
1. How to configure IP addresses in Modbus/TCP?
1. The default IP address of the EX-1130 is 192.168.1.10. You need to change the computer's network segment to 19.168.1.X.
2. Open the IPConfigTool software, select Modbus/TCP, and click Scan Device.
3. Scan for current devices, modify IP addresses, and download configurations.
4. IP address changed successfully.
2. How to configure EIP address?
1. The EX-1121 is manufactured with the 19.168.0.X network segment by default. The computer network segment needs to be changed to match the module network segment.
2. Open the IPConfigTool software, select EtherNet/IP, and click Scan Devices.
3. Scan the module information, double-click EX-1121, and configure the module parameters.
4. Modify the IP address parameters and click OK.
5. IP address changed successfully.
3. How to reset the module?
Manually restore factory settings.
Use a thin screwdriver to press and hold the "RESET" button for 3-5 seconds or more, and wait for the "SYS" indicator light to turn on.
Once the light remains on, release the button; the system will then automatically restore to factory settings.
After the reset is complete, it is recommended to power off the module and then power it back on.
The following parameters will be cleared after the reset operation.
1. Equipment Name;
2. IP address;