1. Error code (D806*): 0000
Error message: NOERROR -- No exception or error occurred.
Abnormal content and cause: No abnormality occurred.
Solution: Please check if the connection between the host and the I/O expansion socket/module is normal.
2. Error code (D8061): 6101
Error message: PLCHARDWAREERROR (PLC hardware failure)
Error message: PLC stopped operating.
Error details and cause: RAM error
Solution: Please check if the connection between the host and the I/O expansion socket/module is normal.
3. Error code (D8061): 6102
Error message: PLCHARDWAREERROR (PLC hardware failure)
Error message: PLC stopped operating.
Cause of the error: Circuit error
Solution: Please check if the connection between the host and the I/O expansion socket/module is normal.
4. Error code (D8061): 6103
Error message: PLCHARDWAREERROR (PLC hardware failure)
Error message: PLC stopped operating.
Error message and cause: I/O Bus error. M8069 must be enabled first for the error to be effective.
Solution: Please check if the connection between the host and the I/O expansion socket/module is normal.
5. Error code (D8061): 6104
Error message: PLCHARDWAREERROR (PLC hardware failure)
Error message: PLC stopped operating.
Cause of the error: The I/O expansion socket is experiencing a 24V fault. M8069 must be turned ON first for the error to be effective.
Solution: Please check if the connection between the host and the I/O expansion socket/module is normal.
6. Error code (D8061): 6105
Error message: PLCHARDWAREERROR (PLC hardware failure)
Error message: PLC stopped operating.
Cause of the error: Watchdog timer malfunction.
Solution: Please check if the connection between the host and the I/O expansion socket/module is normal.
7. Error number (D8062): 6201
Error message: PLC/PPCOMMUNICATIONERROR (PLC/writer communication error)
Error message: Parity/FrameError
Solution: Please check if the connection between the host and the 20P or PC is normal.
8. Error code (D8062): 6202
Error message: PLC/PPCOMMUNICATIONERROR (PLC/writer communication error)
Error message: Abnormal communication phrase
Solution: Please check if the connection between the host and the 20P or PC is normal.
9. Error code (D8062): 6203
Error message: PLC/PPCOMMUNICATIONERROR (PLC/writer communication error)
Error message: Inconsistent communication data check
Solution: Please check if the connection between the host and the 20P or PC is normal.
10. Error code (D8062): 6204
Error message: PLC/PPCOMMUNICATIONERROR (PLC/writer communication error)
Error message: Communication string error
Solution: Please check if the connection between the host and the 20P or PC is normal.
11. Error code (D8062): 6205
Error message: PLC/PPCOMMUNICATIONERROR (PLC/writer communication error)
Error message: Communication command error.
Solution: Please check if the connection between the host and the 20P or PC is normal.
12. Error code (D8063): 6301
Error message: PARALLELLINKERROR (Parallel communication error)
Error message: Parity/FrameError
Countermeasures: Check if the power supplies to both PLCs are on, and whether the connection cables between the main unit and the parallel-operating modules are correctly connected.
13. Error code (D8063): 6302
Error message: PARALLELLINKERROR (Parallel communication error)
Error message: Abnormal communication phrase
Countermeasures: Check if the power supplies to both PLCs are on, and whether the connection cables between the main unit and the parallel-operating modules are correctly connected.
14. Error code (D8063): 6303
Error message: PARALLELLINKERROR (Parallel communication error)
Error message: Inconsistent communication data check
Countermeasures: Check if the power supplies to both PLCs are on, and whether the connection cables between the main unit and the parallel-operating modules are correctly connected.
15. Error code (D8063): 6304
Error message: PARALLELLINKERROR (Parallel communication error)
Error message: Communication string error
Countermeasures: Check if the power supplies to both PLCs are on, and whether the connection cables between the main unit and the parallel-operating modules are correctly connected.
16. Error code (D8063): 6305
Error message: PARALLELLINKERROR (Parallel communication error)
Error message: Communication command error.
Countermeasures: Check if the power supplies to both PLCs are on, and whether the connection cables between the main unit and the parallel-operating modules are correctly connected.
17. Error code (D8063): 6306
Error message: PARALLELLINKERROR (Parallel communication error)
Error message: Monitoring time exceeded
Countermeasures: Check if the power supplies to both PLCs are on, and whether the connection cables between the main unit and the parallel-operating modules are correctly connected.
18. Error code (D8063): 6312
Error message: PARALLELLINKERROR (Parallel communication error)
Error message: Parallel operation clause error.
Countermeasures: Check if the power supplies to both PLCs are on, and whether the connection cables between the main unit and the parallel-operating modules are correctly connected.
19. Error code (D8063): 6313
Error message: PARALLELLINKERROR (Parallel communication error)
Error message: Inconsistent parallel operation overall check
Countermeasures: Check if the power supplies to both PLCs are on, and whether the connection cables between the main unit and the parallel-operating modules are correctly connected.
20. Error code (D8063): 6314
Error message: PARALLELLINKERROR (Parallel communication error)
Error message: Parallel string execution error
Countermeasures: Check if the power supplies to both PLCs are on, and whether the connection cables between the main unit and the parallel-operating modules are correctly connected.
21. Error code (D8064): 6401
Error message: PARAMETERERROR (Incorrect parameter)
Error message: Program integration check inconsistency
Solution: Switch the PLC to STOP mode and check if the parameter settings are correct.
22. Error code (D8064): 6402
Error message: PARAMETERERROR (Incorrect parameter)
Error message: Memory capacity setting is incorrect.
Solution: Switch the PLC to STOP mode and check if the parameter settings are correct.
23. Error code (D8064): 6403
Error message: PARAMETERERROR (Incorrect parameter)
Error message: Incorrect power outage protection zone setting.
Solution: Switch the PLC to STOP mode and check if the parameter settings are correct.
24. Error code (D8064): 6404
Error message: PARAMETERERROR (Incorrect parameter)
Error message: Annotation area setting is incorrect.
Solution: Switch the PLC to STOP mode and check if the parameter settings are correct.
25. Error code (D8064): 6405
Error message: PARAMETERERROR (Incorrect parameter)
Error message: File temporary storage area is incorrectly set.
Solution: Switch the PLC to STOP mode and check if the parameter settings are correct.
26. Error code (D8064): 6409
Error message: PARAMETERERROR (Incorrect parameter)
Error message: Other settings are incorrect.
Solution: Switch the PLC to STOP mode and check if the parameter settings are correct.
27. Error code (D8065): 6501
Error message: SYNTAXERROR (PLC stopped operating, grammar error)
Error message: Incorrect combination of instruction and operand.
Solution: Please check whether each instruction in the program is used correctly.
28. Error code (D8065): 6502
Error message: SYNTAXERROR (PLC stopped operating, grammar error)
Error message: No OUTT or OUTC commands were specified before the set value.
Solution: Please check whether each instruction in the program is used correctly.
29. Error code (D8065): 6503
Error message: SYNTAXERROR (PLC stopped operating, grammar error)
Error message: No set value after OUTT,OUTC; Insufficient number of operands for the applied instruction.
Solution: Please check whether each instruction in the program is used correctly.
30. Error code (D8065): 6504
Error message: SYNTAXERROR (PLC stopped operating, grammar error)
Error message: Number P is used repeatedly; interrupt insertion input number and high-speed counting input number are used repeatedly.
Solution: Please check whether each instruction in the program is used correctly.
31. Error code (D8065): 6505
Error message: SYNTAXERROR (PLC stopped operating, grammar error)
Error message: The specified component is out of range.
Solution: Please check whether each instruction in the program is used correctly.
32. Error code (D8065): 6506
Error message: SYNTAXERROR (PLC stopped operating, grammar error)
Error message: Using an undefined instruction
Solution: Please check whether each instruction in the program is used correctly.
33. Error code (D8065): 6507
Error message: SYNTAXERROR (PLC stopped operating, grammar error)
Error message: P number is incorrect.
Solution: Please check whether each instruction in the program is used correctly.
34. Error code (D8065): 6508
Error message: SYNTAXERROR (PLC stopped operating, grammar error)
Error message: Number I is incorrect.
Solution: Please check whether each instruction in the program is used correctly.
35. Error code (D8065): 6509
Error message: SYNTAXERROR (PLC stopped operating, grammar error)
Error message: Other
Solution: Please check whether each instruction in the program is used correctly.
36. Error code (D8065): 6510
Error message: SYNTAXERROR (PLC stopped operating, grammar error)
Error message: Incorrect use of the N number in MC/MCR.
Solution: Please check whether each instruction in the program is used correctly.
37. Error code (D8065): 6511
Error message: SYNTAXERROR (PLC stopped operating, grammar error)
Error content interruption, insertion of input terminal number, and repeated use of high-speed counting input terminal number.
Solution: Please check whether each instruction in the program is used correctly.