How to change the built-in analog input of a Mitsubishi PLC function module to a current input?

2026-04-06 06:42:01 · · #1

The Mitsubishi FX5U CPU module has a built-in analog input that is a voltage input (DC 0~10V).

This method can convert the signal into an analog current input (DC 4~20m).

[Methods used in current input (DC 4~20mA)]

The FX5UCPU module only supports voltage input, but it can be used as a current input by connecting a 250Ω resistor (0.5% precision resistor) between the V□+ and V- terminals.

1. Wiring Example

The □ in V□+,CH□ represents the CH number.

*1 A 500Ω resistor can also be connected in parallel. Please select a suitable resistor after considering the maximum input current.

*2 For channels that are not in use, short-circuit the “V□+” and “V-” terminals.

2. Standards

Analog input: DC 4~20mA

Digital output value: 400~2000*1

Resolution: 10μA

Maximum input: -2mA, +60mA

The scaling function can be used to change this.

3. Example of using the share scaling function

The default value (upper limit 4000, lower limit 0) is converted to a value (upper limit 4500, lower limit -500) using the share scaling function.