What causes the inverter output module of a frequency converter to fail?

2026-04-06 03:21:16 · · #1

Introduction: After many years of operation, the insulation of the windings of a motor has been greatly reduced due to factors such as temperature rise and moisture, and there may even be obvious insulation defects, putting it at the critical point of voltage breakdown.

I. Damage Caused by Abnormal Load Admittedly, the protection circuits of frequency converters are quite sophisticated. For the protection of expensive inverter modules, various frequency converter manufacturers have put considerable effort into their protection circuits, from output current detection to IGBT voltage drop detection in the drive circuit, striving for the fastest possible overload protection! From voltage detection to current detection, from module temperature detection to phase loss output detection, no other electrical appliance's protection circuit is as focused and dedicated as that of frequency converters. And frequency converter salespeople, when discussing the performance of frequency converters, invariably mention their protection functions, often unconsciously promising users: "With the comprehensive protection functions of a frequency converter, your motor won't easily burn out." This salesperson doesn't realize that this promise will bring them significant trouble!

Will motors really not burn out when using a frequency converter? My answer is: compared to mains power, motors are actually more prone to burning out when using a frequency converter. And this increased risk of motor burnout also makes the frequency converter's inverter module more likely to fail. The frequency converter's sensitive overcurrent protection circuit is completely ineffective in this situation. This is a major external cause of frequency converter module damage. Let me explain why.

A motor can run at mains frequency, although the operating current is slightly higher than the rated current, and there is a certain temperature rise after prolonged operation. This is a faulty motor; it could indeed run before burning out. However, after connecting it to a frequency converter, it experiences frequent overloads, eventually stopping it from running. This isn't a major issue, though.

A motor, which has been running normally at its base frequency for many years (note the word "many years"), is being upgraded to a frequency converter to save on electricity costs or for process improvements. However, after connecting the frequency converter, it frequently trips the overcurrent (OC) fault, which is good because the protection shuts down and the module isn't damaged. The scary part is that the frequency converter doesn't immediately trip the OC fault; instead, it runs inexplicably—after only two or three days, the module explodes, and the motor burns out. The user then blames the salesperson: "The frequency converter you installed is of poor quality; it burned my motor, you have to compensate me for it!"

Before this, the motor seemed to be working perfectly, running smoothly. Measuring the operating current showed it only reached half of its rated current due to the light load; the three-phase power supply was measured at 380V, perfectly balanced and stable. It really seems like the inverter failed, causing damage to the motor in the process.

If I were there, I would say this to my master: Don't blame the inverter; your motor was already "terminally ill," and when it suddenly malfunctioned, it damaged the inverter in the process!

The motor, after years of operation, has experienced a significant reduction in winding insulation due to factors such as temperature rise and moisture absorption, even exhibiting obvious insulation defects and teetering on the brink of voltage breakdown. Under mains frequency power supply, the motor windings are input with a three-phase 50Hz sinusoidal voltage, resulting in low induced voltage and minimal surge components in the line. The reduced insulation may only cause a negligible leakage current, but voltage breakdown between turns and phases has not yet occurred, and the motor continues to operate normally. It should be said that as insulation aging deepens, even under mains frequency power supply, this motor will eventually burn out in the near future due to voltage breakdown between phases or windings caused by insulation aging. However, the problem is that it has not burned out yet.

After connecting the frequency converter, the power supply conditions for the motor become "deteriorated": the PWM waveform output by the frequency converter is actually a carrier voltage of several kHz or even tens of kHz, which will generate various harmonic voltage components in the motor winding power supply circuit. As can be seen from the characteristics of inductance, the faster the rate of change of the current flowing through the inductor, the higher the induced voltage of the inductor. The induced voltage of the motor winding is higher than that under mains frequency power supply. Insulation defects that are not exposed under mains frequency power supply cannot withstand the impact of the induced voltage under high-frequency carrier, thus causing voltage breakdown between turns or phases of the winding. Short circuits between phases or turns in the motor winding cause a sudden short circuit in the motor winding, resulting in the module exploding and the motor burning out during operation.

During the initial startup phase of a frequency converter, because the output frequency and voltage are both within a relatively low amplitude, a fault in the load motor will cause a large output current, but this current is usually within the rated value. The current detection circuit will activate in time, and the frequency converter will implement protective shutdown, preventing the module from being destroyed. However, if the inverter is running at full speed (or near full speed), the three-phase output voltage and frequency will both reach a high amplitude. If there is a voltage breakdown in the motor windings, a huge surge current will be generated instantaneously. The inverter module will be unable to withstand this surge current and will be destroyed before the current detection circuit activates.

This shows that protection circuits are not omnipotent; every protection circuit has its weaknesses. Inverters are powerless against sudden voltage breakdowns in motor windings during full-speed operation, and therefore cannot provide effective protection. Furthermore, not only inverter protection circuits, but no motor protector can effectively protect against such sudden faults. When such a sudden fault occurs, it can only be concluded that the motor has indeed reached the end of its service life.

Such faults are a fatal blow to the inverter output module of the frequency converter, and there is no escaping it.

Other faults caused by power supply or load issues, such as overvoltage, undervoltage, heavy load, or even overcurrent caused by stalled rotor, can effectively protect the module's safety provided the inverter's protection circuit is functioning properly, greatly reducing the probability of module damage. These will not be discussed further here.

II. Module Damage Caused by Inverter Circuit Malfunctions 1. A faulty drive circuit can cause primary damage to the module. As the drive circuit is powered, it typically uses two power supplies: a positive and a negative one. The +15V voltage provides the IGBT transistor's excitation voltage, enabling it to turn on. The -5V voltage provides the IGBT transistor's cutoff voltage, ensuring reliable and rapid cutoff. When the +15V voltage is insufficient or lost, the corresponding IGBT transistor cannot turn on. If the drive circuit's module fault detection circuit can also detect the IGBT transistor, then as soon as the inverter receives a running signal, the module fault detection circuit will report an OC signal, and the inverter will implement a protective shutdown action, posing almost no harm to the module.

However, if the -5V cutoff voltage is insufficient or lost (similar to a three-phase rectifier bridge, we can consider the inverter output circuit as an inverter bridge, with IGBTs forming three upper and three lower arms, such as the IGBTs in the U-phase upper and lower arms), when any phase's upper (lower) arm is activated and turned on, the corresponding lower (upper) arm IGBT will, due to the loss of cutoff voltage, experience charging of the gate-emitter junction capacitance by the collector-gate junction capacitance of the IGBT, leading to mis-conduction of the transistor. This, combined with the short circuit between the two transistors, creates a short circuit in the DC power supply! The consequence is: the entire module will explode!

The loss of cutoff negative voltage can be caused by several factors: a damaged driver IC; a damaged lower transistor in the power drive stage (usually composed of two complementary voltage follower power amplifiers); a poor connection in the trigger terminal leads; or a faulty negative power supply branch in the drive circuit or a failed power supply filter capacitor. If any of these issues occur, it will be a fatal blow to the module, and the damage will be irreversible.

2. A faulty pulse transmission path will also pose a threat to the module.

The six PWM inverter pulses output by the CPU typically pass through six inverting (or non-inverting) buffers before being sent to the input pins of the driver IC. From the CPU to the driver IC, and then to the trigger terminals of the inverter module, if any one of the six signals is interrupted—

(1) The inverter may report an OC fault. The voltage drop of the IGBTs in the lower three arms of the inverter bridge when they are turned on is detected and processed by the module fault detection circuit. However, in a small number of inverters, the voltage drop detection circuit for the IGBTs in the upper three arms is detected, but in most inverters, the voltage drop detection circuit is omitted. If the IGBT that loses the excitation pulse happens to have a voltage drop detection circuit, the detection circuit will report an OC fault after the excitation pulse is lost, and the inverter will shut down for protection.

(2) The inverter may experience phase misalignment. The IGBT tube that loses the excitation pulse is the one without a voltage drop detection circuit. Only the negative cutoff voltage exists to reliably cut it off. The bridge arm of that phase only has a half-wave output, causing the inverter to operate in phase misalignment. As a result, a DC component is generated in the motor winding, which also forms a large surge current, causing the module to be damaged by the impact! However, the probability of damage is lower than that of the first reason.

If this pulse transmission path is always open, even if the module fault circuit cannot function, the current detection circuit such as the current transformer can still function and provide protection. However, the problem is that this transmission path may be intermittent due to faults such as poor contact, or even random interruptions. The current detection circuit may not be able to react in time, causing the inverter to output "intermittent phase bias", resulting in a large inrush current and damaging the module.

In this output state, the motor will "jump" and make a "clunking" sound, and the heat generation and losses will increase significantly, making it easy to be damaged.

3. Failure or malfunction of the current detection circuit and module temperature detection circuit will prevent the module from effectively protecting against overcurrent and overheating, thus causing damage to the module.

4. When the capacity of the energy storage capacitor in the main DC circuit decreases or fails, the pulsating component of the DC circuit voltage increases. This is not obvious when the inverter is started under no-load or no-load conditions, but during the start-up under load, the circuit voltage surges and the inverter module explodes and is damaged. The protection circuit is also helpless in the face of this.

For frequency converters that have been in operation for many years, the capacity of the DC circuit's energy storage capacitor should not be overlooked after a module failure. Complete capacitor loss is rare, but if it does occur, it will undoubtedly damage the inverter module during load startup!

Thirdly, the existence of a small number of domestically produced frequency converters of inferior quality and made with substandard materials, whose modules are extremely prone to damage, reflects a deep-seated national weakness and a sense of national insecurity. It's true that competition in the frequency converter market has intensified in recent years, and profit margins have become increasingly narrow. However, competitiveness can be improved through technological advancements and increased productivity. Using methods such as passing off old products as new, substandard materials, and reducing module capacity to increase market share is unwise and a short-sighted, short-term strategy.

1. Poor quality and shoddy manufacturing increase the failure rate of the inverter's fault protection circuit. As the inverter module is not effectively protected by the protection circuit, the probability of module damage increases.

2. The capacity of the inverter module should generally be at least 2.5 times the rated current to ensure long-term safe operation. For example, a 30kW inverter with a rated current of 60A should use a 150A to 200A module. A 100A module is too small. However, some manufacturers dare to use 100A modules! Even worse, some use old or substandard modules. Such inverters are not only prone to module damage during operation, but the modules often explode during startup! On-site installers of such inverters are terrified, using a wooden stick to press the start button on the control panel from a distance.

If a module with a small capacity can barely operate, it will be overloaded, rendering the protection circuit ineffective (protection is based on the inverter's rated power capacity instead of the module's actual capacity). It would be abnormal if the module did not frequently explode.

These machines seemed to be very popular when they first came out due to their low price, but it didn't last long before the manufacturers had no choice but to go bankrupt.

This third reason for module failure shouldn't even be a cause. Hopefully, in the near future, only the first two reasons will remain as causes for module failure.

For domestically produced frequency converters, sometimes a single bad apple spoils the whole bunch. Many frequency converters are actually quite good, comparable to foreign products, and offer excellent quality at a lower price.

Read next

CATDOLL 123CM Momoko (TPE Body with Soft Silicone Head)

Height: 123cm Weight: 23kg Shoulder Width: 32cm Bust/Waist/Hip: 61/54/70cm Oral Depth: 3-5cm Vaginal Depth: 3-15cm Anal...

Articles 2026-02-22
CATDOLL Kara TPE Head

CATDOLL Kara TPE Head

Articles
2026-02-22
CATDOLL 128CM Yuki

CATDOLL 128CM Yuki

Articles
2026-02-22
CATDOLL 136CM Tami

CATDOLL 136CM Tami

Articles
2026-02-22