Wind power generation technology and power semiconductor devices and control systems
2026-04-06 05:59:44··#1
Harnessing solar energy through wind is not a new concept, but today's power semiconductor devices and control systems make this energy source even more readily applicable. Among existing solar energy utilization technologies, wind turbines have become pioneers in large-scale "green electricity" production. Today, the US and European governments are strongly supporting the production of sustainable energy. In 2003, the total installed capacity of wind farms in the US reached $1.6 billion, and it is projected that by 2020, an additional 100,000 MW of installed capacity will be added, meeting 6% of US electricity demand. The US will also build the world's largest ground-mounted wind farm in Tehachapi in the Majave Desert. However, data from 2002 shows that 90% of the new capacity globally is still in Europe. Variable energy input poses a challenge for designers . It is beneficial to accurately assess the extent to which pioneers solved many of the problems that plague designers today. Among these problems, the greatest is the variability of energy supply. Conventional steam turbine power plants use four key mechanisms to regulate generator speed and power output: the primary energy consumption rate for steam production; the rate at which steam is delivered to the turbine; the level of electrical excitation in the generator; and variations in the rotor load angle. Such generators are synchronous generators, where the rotor is synchronized with and rotates at an integer multiple of the grid frequency. Changing the rotor's angle relative to its zero-phase-difference "no-load" position increases or decreases the electrical energy supplied to or from the grid, thus operating the generator or motor respectively. In typical generator operation, the rotor leads the grid by approximately 30°. Because the power output is directly coupled to the grid, the generator shaft torque provided by strong grid conditions controls its speed, maintaining a constant grid frequency. So, how much power can wind turbines produce? Theory shows that, given air density, the usable watts per square meter vary with the cube of the airflow. Therefore, rotor performance is crucial to every aspect of wind turbine generator design. One critical parameter is the tip speed ratio, which is the ratio of the blade tip speed to the free-flowing air velocity. This parameter describes the rotor's power coefficient, which German physicist Albert Betz believed in 1919 could not exceed 0.593. In practice, a typical rotor power coefficient rarely exceeds 0.4 when the tip speed ratio is 7 (Figure 1). If the rotor speed is constant and efficiency losses are negligible, you can calculate the power output of a wind turbine generator using the following formula: Power = Cp × r / 2 × V³W × A Where CP is the rotor's power coefficient, r is the air density (kg/m³), vw is the wind speed (m/s), and A is the area swept by the rotor (m³). Therefore, it is beneficial to consider the wind turbine generator based on the area swept by the rotor and the kilowatts of power generated per hour. The designer's task is to find the optimal combination of rotor structure and generator principle at a reasonable price for mass production, thereby achieving the maximum overall power coefficient. Practical wind turbine generators have output power ranging from 20 kW to 30 kW, with current high levels reaching 4.5 MW. It typically uses a three-bladed rotor because experiments have shown that this structure provides the optimal balance between efficiency, dynamic performance, and structural economy. The core components generally include the rotor, a gearbox that increases the generator shaft speed, the generator, the circuit interface, and the control loop (Figure 2). The biggest challenge has always been stabilizing the rotor speed to achieve maximum power generation. While a wind turbine generator is a mechatronic system, making it impossible to isolate the individual critical components, the rotor control principle is a decisive factor. The control system must protect the machine from various conditions, ranging from stillness to gales that may only occur once a century, with varying directions and speeds. As an indicator of relevant quality, the rotor assembly of Vestas' V90 series 3MW wind turbine generator weighs 40 tons, despite its use of many expensive carbon fiber composite materials. The simplicity of stall control masks the problem . One method of limiting power acquisition is to rotate the rotor assembly to a position unaffected by the wind. A deflection system, typically used to keep the rotor facing the wind, includes a wind speed sensor, a wind direction sensor, an electric or hydraulic motor drive, interface circuitry, and gears and bearings that rotate the generator nacelle. The sensor assembly is often located behind the generator nacelle and is typically a three-ring anemometer with a wind vane. Other technologies include ultrasonic devices, such as the pair of ultrasonic units used on Vestas' V90-3.0MW. In reality, the wind speed behind the rotor is slightly lower than the actual wind speed due to the localized low-pressure effect of the rotating blades. While this difference is not significant, characterization can compensate for such errors. However, since experience shows that speed control using a deflection system is not very effective, designs generally either maintain the maximum power position facing the wind or turn the generator nacelle to the direction of minimum wind power to achieve shutdown. The simplest aerodynamic method for stabilizing energy harvesting is passive stall (stop) control with a fixed rotor tilt angle. At a given rotor speed, an increase in wind speed causes the airflow to disperse across the blade surface, creating a stall effect. This airflow dispersion automatically limits energy harvesting but is related to air density and the polishing quality of the blade surfaces. This method also requires robust grid conditions and a powerful generator to maintain stability. If the grid connection fails or a power outage occurs, rotor overspeed must be prevented, requiring pneumatic brakes on the rotor and conventional disc brakes on the input shaft. Because the rotor has a fixed tilt angle and cannot be rotated to its maximum torque position for starting, it is sometimes necessary to operate the generator in motor mode to accelerate the rotor to a speed synchronized with the grid. Finally, the structure must be robust enough to withstand the large dynamic loads characteristic of stall control. Despite this, some successful wind turbine generators have adopted this principle. Nordic WindPower's Model 1000 1MW wind turbine generator, simple and lightweight, uses a two-bladed stall-controlled rotor with a swept area of 2290 m². This turbine generator is self-starting and has stall bars on the blades to reduce the peak power curve of some early stall-controlled turbine generators, thus achieving a flat-topped power curve. The rotor uses a glass fiber reinforced polyester structure because this structure has good aerodynamic elasticity, which is beneficial for a "soft" or "flexible" structure to absorb large dynamic loads. Borrowing other helicopter components, including a "seesaw" hub with elastic bearings, allows for ±2° relative movement between the blades and the input shaft, reducing wind shear forces. Additional damping in the generator and yaw control systems further enhances the structure's flexibility. The generator, manufactured by Weier Electronics, is a four-pole single-speed induction generator with a rotor that rotates slightly faster than the rotating electromagnetic field. This "slip" provides damping, helping to suppress electromechanical oscillations. This slip value varies from 1% to 10% simply by switching the resistance within the generator rotor circuit to control the excitation current. Since the torque of an induction generator is proportional to the slip, this provides speed control, a function difficult to achieve with asynchronous generators. At 0% slip, the generator is synchronized with the grid frequency, neither generating nor consuming power (except for reactive power consumed by the rotor). Similarly, if the generator speed is lower than the grid frequency, it enters motor mode and draws current from the grid. To limit this current consumption, input shaft disc brakes typically prevent rotor movement at wind speeds below approximately 4-5 m/s (the so-called cut-in speed of the turbine generator). Vestas also applies slip control technology to its OptiSlip system, with optical coupling between the rotor's electronic circuitry and the stator's controller. In this example, the control value is approximately 10%, with an operating time of approximately 10 ms, achieving smooth power output under turbulent conditions and reducing structural load. Slip also affects generation efficiency; megawatt-class generators typically operate with slip within the 1% range, achieving an efficiency of approximately 95%. Because rotor circuitry consumes reactive power, the power factor is generally low, around 0.87. For this reason, switched capacitor banks are an integral part of traditional systems, but power circuitry increasingly controls the power factor. In the case of Nordic's Model 1000 turbine generator, switched capacitors maintain the output power factor at 1 throughout the turbine generator's operating range. By introducing damping factors into the control loop of the deflection system, it is possible to cause the blades to oscillate around the tower axis to a certain extent, thereby absorbing turbulence. Therefore, the 1000 turbine generator structure can withstand wind speeds of 55 m/s, starting operation at 4 m/s and stopping at 25 m/s. At a rotor speed of 25 rpm and a blade tip speed of 71 m/s, the generator can output a maximum power of 1 MW at a wind speed of 17 m/s. When the rotor just begins to overspeed, centrifugal force drives a hydraulic release valve, causing the blade tips to rotate to the braking position. Mita-Teknik, a company specializing in wind power systems, produces SCADA (Management Control and Data Acquisition) systems that can also drive pneumatic and mechanical brakes. The generator outputs 690V three-phase AC power to the tower via a flexible cable. The SCADA system can rewind the cable to prevent tangling. Communication between the SCADA system and central equipment is via a modem and telephone line, and a PC is used to independently monitor and record the turbine generator's operation. Control systems simplify power acquisition. Many wind turbine designers favor rotor tilt angle control technology because it significantly alleviates speed variation and system power acquisition issues. Modern products employ two different tilt angle control methods: the first gradually decreases the blade angle of attack against the airflow from its maximum full-power position to the cyclic pitch position where minimum power is achieved; the second increases the angle of attack until aerodynamic stall occurs. Danish engineers MB Pedersen and P Nielsen tested these two methods in the experimental Nibe-A and Nibe-B turbine generators in 1980 (Reference 1). Their results showed that full-blade tilt angle control resulted in smoother output characteristics and potentially reduced torque thrust at high wind speeds (Figure 3). Today, more advanced blade aerodynamic and control algorithms help reduce the difference between these two approaches. Bonus Energy's CombiStalls active stall design is a prime example. Its "Danish concept" turbine generator includes a three-bladed rotor with a constant rotational speed, a generator that directly supplies power to the grid, and a fail-safe system. The company's largest product is the B40 2.3MW turbine generator, with a rotor sweep area of 5330m². It is possible to rotate the glass fiber reinforced epoxy blades 80° to the stop position. During normal operation, a microprocessor-controlled servo loop continuously adjusts the blades to the stall position. A dual-generator design allows for dual-speed operation (11 rpm or 17 rpm), thereby improving efficiency under partial load. By connecting a six-pole generator winding at low wind speeds, the generator can produce power at two-thirds of its rated speed. At higher wind speeds, the generator can switch to a four-pole main winding and operate at normal speed. The turbine generator can self-start at average wind speeds of approximately 5 m/s to 6 m/s. When a thyristor soft-start circuit connects the generator to the grid, the rotor accelerates to grid synchronization speed. After a few seconds of linear operation, the main contactor bypasses the thyristor circuit to eliminate semiconductor losses. Then, in the maximum wind speed range of approximately 14 m/s to 15 m/s, the power output of the wind turbine generator increases roughly linearly with the maximum wind speed. At this point, the control loop engages to maintain a constant power output and prevent generator overload. If the average wind speed exceeds the turbine generator's operating limits, the control system periodically adjusts the blade pitch and applies brakes to shut down the turbine generator. When the wind speed falls below the restart limit, the safety system automatically resets, and the turbine generator restarts—unless a fault occurs, the turbine generator remains offline. A backup system provides automatic safety operation because it can use a centrifugal device to disable the turbine generator control system in the event of a serious fault. Inverters simplify operation. The most flexible power acquisition and control capabilities come from variable speed operation, as the turbine generator rotor can ideally operate at the maximum blade tip speed ratio. Early attempts to replace the fixed-speed planetary gearbox with an automatic gearbox failed due to cost and reliability issues. Because slip control methods offer only limited speed control for induction generators, many modern turbine generators employ an alternative approach: the DFIG (Doubly-Fed Induction Generator), first used in the 3MW Groveian wind turbine experiment of the 1980s. The Groveian configuration includes a synchronous generator with a three-phase slip-ring fed rotor to produce a rotor-wound induction generator. This setup allows a circulating converter to inject alternating current into the rotor (Figure 4a). The circulating converter, an AC-AC inverter made with a thyristor array, samples the three-phase line frequencies to generate a low-frequency control waveform (Figure 4b). Superimposing this control waveform onto the rotor's electric field helps stabilize the generator's output frequency; controlling the amplitude and phase of this control waveform controls the generator's power factor, thus simulating the synchronous generator's ability to provide both active and reactive power. This configuration also has some drawbacks, one of which is its greater susceptibility to grid faults compared to other configurations. One relatively simple variable-speed technology uses an AC-DC-AC link as the inverter, which first rectifies the generator's "scraggly AC" output and then commutates it at the line frequency. This technology isolates the generator from the load, allowing the use of more efficient synchronous generators and maintaining generator torque control by changing the DC link state. The Vestas V90-3 MW wind turbine is an example, employing full blade angle control and the company's OptiSpeed technology to control the rotor's 6362 m² swept area. The OptiSpeed system allows for a 60% change in rotor and generator speed, minimizing variations in power output to the grid and reducing structural stress. At the heart of this system are the company's VMP-Top controller and inverter, which form the power electronics circuitry used to control the generator and its output to the grid transformer. The wind turbine is otherwise unremarkable, retaining a gearbox to increase generator speed (the generator's original speed range is 9 rpm to 19 rpm). However, in a conceptually simple approach, Enercon pioneered a series of gearless direct-drive wind turbine generators with a rated capacity of up to 4.5MW. In this design, the rotor is mounted directly on the generator, reducing the number of drive train bearings to only two low-speed rotating components. The challenge lies in generating sufficient power at low speeds and optimally converting it to grid frequency. Enercon addresses this by using an electrically excited synchronous generator with numerous electrodes, such as the 4.8m diameter 84-pole electrically excited synchronous generator in their E-40 600kW wind turbine. Here, the rotor speed varies from 18rpm to 34rpm, sweeping an area of 1521m². Leveraging its expertise in industrial variable frequency drive design, Enercon employs its own electronic circuitry. In contrast, Zephyros's newly launched Z72 2MW wind turbine generator, while also featuring a direct-drive generator, utilizes ABB's improved ACS 1000 variable speed motor drive controller. One of the drive shaft bearing supports is also a permanent magnet generator manufactured by ABB. Zyphyros highlighted the advantages of permanent magnet generators when listing their benefits, such as reduced generator losses, excellent part-load efficiency, and lower failure rate. The disadvantage of permanent magnet generators is their high cost due to the use of high-permeability magnetic materials (such as neodymium iron boron and samarium cobalt). Another drawback is their poor power factor characteristics, which must be compensated for by frequency converter circuitry. However, many experts believe that permanent magnet generators are the future, especially for large direct-drive designs. Adrian Wilson, an electrical technology expert at NaREC (New Energy and Renewable Energy Centre) in the UK, says this approach is central to a current research project focused on weight reduction. Because the power output of a wind turbine theoretically increases by the cube of the volume of air it receives, the structural components also increase in weight proportionally. Wilson says that current design methods cannot simply scale up to the 10MW level—let alone the future 20MW or 30MW required—so his department is investigating a direct-drive design that can save gearbox mass. This method also requires a large-diameter generator. At the scale involved in this project, one potentially unconventional approach is to use a bicycle wheel-like structure with spokes supporting the generator's electrode pairs. The grid output connection requires a full-power AC-DC-AC inverter link, which in turn requires multiple parallel inverters. IGBTs Replace SCRs The power semiconductor devices required for wind turbine generators are unfamiliar to those working in microelectronics. You're not considering submicron linewidths, but rather the European standard printed circuit board area (from 34mm × 94mm to 140mm × 190mm) occupied by a single device module. Such devices can withstand kiloamperes at thousands of volts, and advancements in this technology over the past few decades have been the greatest contribution to the development of wind turbine generators. In the Growing era, SCR technology could handle high-power applications, but it suffered from high conduction losses and poor conversion time performance, often in the range of 100ms. Correspondingly, the inverter stage uses a waveform with 6 or 12 steps to approximate a sine wave energy distribution, resulting in particularly strong odd harmonics, such as the fifth and eleventh harmonics. These limitations necessitate the use of harmonic frequency filters. Replacing Groenian's first-generation thyristors with IGBTs (Insulated Gate Bipolar Transistors) allows for pulse width modulation (PWM) to overcome poor harmonic performance. This technology also makes the control of actual power and reactive power more convenient. Although traditional thyristors are durable, and modern thyristors, such as Mitsubishi's FT1500AU-240, can switch 1.5kA of current at 12kV with a switching time of 15ms, traditional thyristors cannot turn off when the conduction current exceeds the holding current value. Gate turn-off (GTO) thyristors (such as Mitsubishi's FG6000AU-120D) can continuously provide 6 kV and 1.5 kA of current, and can achieve turn-off control within 30 ms, but they are difficult to drive. Worse still, all thyristors are difficult to parallelize, yet parallel operation is often indispensable to achieve the power levels required by wind turbine generators. High-power IGBTs combine the ease of driving and current-sharing characteristics of MOSFETs with a 1 ms switching time. Although the PWM frequency required to switch the line frequency is low, only a few kilohertz, this fast switching reduces conduction losses as the IGBT traverses its linear operating region. Devices such as Euec's FZ600R65KF1 have a turn-on time of less than 1 ms and a turn-off time of less than 6 ms, and can control 1.2 kA of current at 6 kV; low-voltage devices such as Euec's FZ3600R12KE3 can switch 3.6 kA of current at 1.2 kV. Therefore, IGBTs can be used in high-power frequency converters and soft-start controllers. Other companies specializing in high-power semiconductor devices include ABB, Dynex, Fujitsu Electronics, Powerex, and Semikron. Gamesa Etsuba's wind turbine generator series, ranging from 660kW to 2MW, extensively utilizes IGBT technology for variable speed and frequency control. Variable tilt angle rotor blade control allows for continuous adjustments to achieve maximum power and can be coupled to a DFIG system with a generator speed range of 900rpm to 1900rpm. This control technology minimizes peak power, flicker, and harmonics, thus facilitating grid connection permitting. Vector control systems can generate or dissipate reactive power, precisely adjusting the power factor to improve grid voltage stability. Gamesa Etsuba's power circuitry also enables its turbines to remain online when power outages occur elsewhere in the grid. Economically, these issues are critical in Spain, where additional tariffs are levied on high-quality grid connections. Ivan Novikoff, head of the wind energy division at the French company Cegele, points out that the selection of wind turbine generators and their technologies depends primarily on the location and characteristics of the local infrastructure. Novikoff says that issues such as cable laying, starting current, and short-circuit current all depend on the system structure. When developing specifications for wind turbine generators for known applications, the company considers many secondary but essential factors, ranging from permissible rotor height and noise radiation to the quality of the manufacturer's on-site service. Novikoff explains that from an investor's perspective, machine economic factors to consider include the reliability of wind power supply, machine reliability and maintenance costs, and differences in electricity production tariffs. Reference: Pedersen, MB and P Nielsen, "Description of two Danish 630 kW wind turbines Nibe A and Nibe B, Copenhagen," Third British Hydromechanics Research Association International Symposium on Wind Energy Systems, 1980.