The P01 basic function group of the OKE frequency converter mainly includes the following functions: control mode; operation command channel; encoder and terminal increment/decrement setting; frequency command selection; torque setting method selection; keypad torque setting; upper limit frequency setting source selection; maximum output frequency; upper limit operating frequency; lower limit operating frequency; keypad frequency setting; acceleration time 1; deceleration time 1; running direction selection; carrier frequency setting; function parameter recovery; AVR function selection.
P01 group basic function group
1 | P01.00 | Control Mode | 0: V/F control 1: Open-loop flux vector control 1 2: Open-loop flux vector control 2 3: Sensor feedback closed-loop vector control | 0 | □ | 59 |
2 | P01.01 | Run command channel | 0: Keyboard command channel (LED off) 1: Terminal command channel (LED flashing) 2: Communication command channel (LED lit) | 0 | □ | 59 |
3 | P01.02 | Encoder and terminal increment +/decrement - settings | 0: Valid, and the inverter stores the value after power failure. 1: Effective, and the inverter does not store data when power is off. 2: Increment +/Decrement - settings are invalid 3: Settings are valid during runtime and reset upon shutdown. | 0 | ◇ | 59 |
4 | P01.03 | Frequency command selection | 0: Keyboard Settings 1: Analog AI1 settings 2: Analog AI2 Settings 3: K1*AI1+K2*AI2 4: Multi-speed operation setting 5: PID control settings 6: Remote Communication Settings 7: Keyboard potentiometer setting | 7 | ◇ | 60 |
5 | P01.04 | Torque setting method selection | 0: Keyboard-set torque (corresponds to P01.05) 1: Analog signal AI1 sets the torque (100% relative to twice the inverter's rated current) 2: Analog input AI2 sets the torque (same as 1) 3: Analog inputs AI1 and AI2 set the torque (same as 1) 4: Multi-stage torque setting (same as 1) 5: Remote communication to set torque (same as 1) | 0 | ◇ | 60 |
6 | P01.05 | Keyboard setting torque | -200.0%~200.0% (inverter rated current) | 50.0% | ◇ | 60 |
7 | P01.06 | Upper limit frequency setting source selection | 0: Keyboard setting upper limit frequency (P01.07) 1: Set the upper limit frequency for analog signal AI1 (100% corresponds to the maximum frequency). 2: Set the upper limit frequency for analog signal AI2 (same as 1) 3: Multiple frequency limits can be set (same as 1) 4: Set the maximum frequency for remote communication (same as 1) | 0 | ◇ | 61 |
8 | P01.07 | Maximum output frequency | 10.00~400.00Hz | 50.00Hz | □ | 61 |
9 | P01.08 | Operating frequency limit | P01.09~P01.07 (maximum frequency) | 50.00Hz | ◇ | 61 |
10 | P01.09 | Operating frequency lower limit | 0.00Hz~P01.08 (Upper limit of operating frequency) | 0.00Hz | ◇ | 61 |
11 | P01.10 | Keyboard setting frequency | 0.00 Hz~P01.07 (maximum frequency) | 50.00Hz | ◇ | 61 |
12 | P01.11 | Acceleration time 1 | 0.1~3600.0s | Model settings | ◇ | 61 |
13 | P01.12 | Deceleration time 1 | 0.1~3600.0s | Model settings | ◇ | 61 |
14 | P01.13 | Running direction selection | 0: Default direction of operation 1: Running in the opposite direction 2: Reverse operation is prohibited. | 0 | □ | 62 |
15 | P01.14 | Carrier frequency setting | 0.5~15.0kHz | Model settings | ◇ | 62 |
16 | P01.15 | Function parameter recovery | 0: No operation 1: Restore default values excluding motor parameter groups 2: Restore default values, including motor parameter groups. 3: Clear fault files | 0 | □ | 62 |
17 | P01.16 | AVR Function Selection | 0: Invalid 1: Valid throughout the entire process 2: Only ineffective during deceleration | 2 | ◇ | 62 |
Serial Number | code | Description of LED/OLED Keyboard display | Set range | Factory settings | Change | Reference Page |