The OKE inverter P02 start/stop control group mainly has the following functions: P02.00 Start-up mode; P02.01 Start-up frequency; P02.02 Start-up frequency holding time; P02.03 Pre-start braking current; P02.04 Pre-start braking time; P02.05 Stop mode selection; P02.06 Stop braking start frequency; P02.07 Stop braking waiting time; P02.08 Stop DC braking current; P02.09 Stop DC braking time; P02.10 Forward/reverse dead time; P02.11 Power-on terminal operation protection selection; P02.12 Reserved
P02 group start/stop control group
1 | P02.00 | Startup and running methods | 0: Start directly 1: Apply DC braking first, then start. 2: Speed tracking restart | 0 | □ | 63 |
2 | P02.01 | Startup frequency | 0.00~10.00Hz | 0.50Hz | ◇ | 63 |
3 | P02.02 | Startup frequency retention time | 0.0~50.0s | 0.0s | ◇ | 63 |
4 | P02.03 | Braking current before start | 0.0~150.0% | 0.0% | ◇ | 63 |
5 | P02.04 | Braking time before start | 0.0~50.0s | 0.0s | ◇ | 63 |
6 | P02.05 | Shutdown method selection | 0: Decelerate and stop; 1: Free stop | 0 | ◇ | 63 |
7 | P02.06 | Stop mechanism start frequency | 0.00~P01.07 (maximum frequency) | 0.00Hz | ◇ | 63 |
8 | P02.07 | Stop mechanism waiting time | 0.0~50.0s | 0.0s | ◇ | 63 |
9 | P02.08 | DC braking current during shutdown | 0.0~150.0% | 0.0% | ◇ | 63 |
10 | P02.09 | DC braking time during shutdown | 0.0~50.0s | 0.0s | ◇ | 63 |
11 | P02.10 | Forward and reverse dead zone time | 0.0~3600.0s | 0.0s | ◇ | 63 |
12 | P02.11 | Power-on terminal operation protection selection | 0: Terminal operation command is invalid upon power-on 1: Terminal operation command is valid upon power-on. | 0 | ◇ | 64 |
13 | P02.12 | Reserved | ◇ | 64 | ||
Serial Number | code | Description of LED/OLED Keyboard display | Set range | Factory settings | Change | Reference Page |